Recipient

Greater Manchester Fire and Rescue Service

First report 18 Oct 2013•Latest report 4 Mar 2016

Recipient record

Reports, concerns and published responses

Local government · Fire and rescue service. This page brings together reports naming this recipient and response statements clearly connected to concerns raised in those reports.

Reports
3

Naming this recipient

Published responses
33%

Found for named reports

Concerns addressed
5

Across all linked responses

Stated actions
5

Described in responses

Reports over time

Reports over time

Reports naming this recipient by issue year.

Evidence profile

Report topics

Share of this recipient’s reports compared with all other recipients.

33%published responses found
5stated actions described

Topic comparisons are not available in the current evidence snapshot.

Concerns and recipient responses

Statements from Greater Manchester Fire and Rescue Service linked to the concerns in each report. Select any concern, action or position to view the source wording.

  1. Manchester South

    AI-generated summary

    Lee Richard Gaunt · Prevention of Future Deaths report

    This summary was generated using AI from the published report. Please read the original report for the complete account.

    Report summary

    Lee Richard Gaunt went to work a night shift at Stalybridge Fire Station on 17 October 2015 and was later found hanging from a tree at the station. The report raised concerns about limited Occupational Health support, delays in accessing a doctor, additional managerial and emergency-response duties following a colleague’s death, and a general failure to provide support staff in stressful situations.

    Read the report on judiciary.uk

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Delays in access to Occupational Health medical assessment

    Wider context from the report

    “1. There appeared to be rather less than effective support from Occupational Health and it took a long time for the deceased to be able to see the doctor. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Failure to provide support staff in stressful situations

    Wider context from the report

    “4. It became apparent in the course of the evidence, that the deceased and his wife felt there was a general failure by the GMFRS to provide support staff in stressful situations. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Failure to adjust strenuous First-Responder duties for staff experiencing bereavement-related distress

    Wider context from the report

    “3. In the aftermath of the death of his colleague, and whilst being forced to take on the extra Watch Manager job, he was also having to cope with the extra (and as he regarded it, strenuous) task of leading the fire-fighters as First-Responders to assist North West Ambulance Service in attending cardiac arrest calls. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Ineffective Occupational Health support

    Wider context from the report

    “1. There appeared to be rather less than effective support from Occupational Health and it took a long time for the deceased to be able to see the doctor. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Failure to adjust additional managerial duties for staff known to be suffering bereavement-related distress

    Wider context from the report

    “2. Whilst it was known by the Fire and Rescue Service that he was suffering as a result of the death of his colleague, nonetheless he was required to take on the extra duties of Crew manager and Watch Manager. ”
    Open source report

    Source evidence

    How this respondent action was interpreted

    PFD Monitor created a concise, searchable interpretation from the published response wording shown below.

    PFD Monitor interpretation

    Amend procedures to allow employees to self-refer for counselling through the occupational health provider.

    Verbatim wording from the response

    “3. GMFRS has amended its procedures to allow employees to self-refer for counselling via its occupational health provider.”

    Source location

    Lee-Gaunt-Response
    Page 2 · response
    Published 4 March 2016

    Open published response

    Source evidence

    How this respondent action was interpreted

    PFD Monitor created a concise, searchable interpretation from the published response wording shown below.

    PFD Monitor interpretation

    Retender and operate occupational health provision with triage, escalation and automatic doctor follow-up where required.

    Verbatim wording from the response

    “1. GMFRS’s occupational health providers in 2013 were different to the current providers. GMFRS retendered its occupational health service provision on the expiry of the previous contract on 31 January 2015. The current providers are Healthwork and you heard from one of their directors, ████████ at the inquest.”

    Source location

    Lee-Gaunt-Response
    Page 1 · response
    Published 4 March 2016

    Open published response

    Source evidence

    How this respondent action was interpreted

    PFD Monitor created a concise, searchable interpretation from the published response wording shown below.

    PFD Monitor interpretation

    Continue the trade-union working group examining support facilities for stressful situations and informing organisational strategy and structure.

    Verbatim wording from the response

    “In addition to the matters referred to under Concerns 2 & 3, GMFRS established a working group with trade union participation examining the facilities available for addressing the effects of dealing with stressful situations. This working group will continue and seek on-going involvement and contribution from all relevant trade unions and will inform GMFRS’s strategy and new organisational structure in this regard, which is currently under review.”

    Source location

    Lee-Gaunt-Response
    Page 2 · response
    Published 4 March 2016

    Open published response

    Source evidence

    How this respondent action was interpreted

    PFD Monitor created a concise, searchable interpretation from the published response wording shown below.

    PFD Monitor interpretation

    Pilot and evaluate Trauma Risk Management as a proactive, peer-led support system following traumatic events.

    Verbatim wording from the response

    “GMFRS operates a mandatory system of critical incident debriefing following attendance at traumatic incidents. Since November 2015 GMFRS has been piloting a system known as Trauma Risk Management (TRiM) which is a proactive, peer led initiative for supporting individuals following exposure to traumatic events. The TRiM protocol is widely used in the Armed Forces and Police services and is fully compliant with the National Institute of Health & Clinical Excellence (NICE) guidelines for the delivery of post trauma support.”

    Source location

    Lee-Gaunt-Response
    Page 2 · response
    Published 4 March 2016

    Open published response

    Source evidence

    How this respondent position was interpreted

    PFD Monitor created a concise, searchable interpretation from the published response wording shown below.

    PFD Monitor interpretation

    The organisation was unaware that ill health had recurred when additional duties and cardiac-arrest responsibilities were undertaken.

    Verbatim wording from the response

    “Crew Manager. GMFRS was not aware that the deceased had begun to suffer ill health again when he took on additional duties on the retirement of his Watch Manager on 30 August 2015 and the implementation of the collective agreement to respond to cardiac arrests on 15 September 2015.”

    Source location

    Lee-Gaunt-Response
    Page 2 · response
    Published 4 March 2016

    Open published response
  2. Manchester South

    AI-generated summary

    Kenneth George Bailey · Prevention of Future Deaths report

    This summary was generated using AI from the published report. Please read the original report for the complete account.

    Report summary

    Kenneth George Bailey, who had lung cancer and was dependent on oxygen at home, died after dropping a cigarette or ash onto a kitchen roll, causing a house fire and significant smoke inhalation. The report raised concerns about the limited opening hours of the local fire station, delays in emergency-service arrival, and the risk that unqualified members of the public might attempt rescues.

    Read the report on judiciary.uk

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Insufficient manning of the local fire station

    Wider context from the report

    “During the course of the evidence I was told of the efforts of neighbours and others to attempt a rescue, which to some extent they were able to do. One reason for this attempted rescue was because of the time lapse in getting fire appliances to the scene. I was informed that there is a Fire Station in Mossley, Ashton u Lyne, but this is only manned during very limited opening hours. I was also informed that there is a significant body of volunteers prepared to act as local volunteer fire officers. Because the fire station was not manned, it took approximately 10 minutes for the fire service to arrive, and whilst this is of course reasonably fast, the local people felt the response time used to be quicker when the local “station” was open. If there is a delay in the arrival of the emergency services, there is always the danger that unqualified people will try to perform a rescue thus placing themselves in danger of injury or even death. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Danger of unqualified people attempting rescue during delayed emergency-service arrival

    Wider context from the report

    “During the course of the evidence I was told of the efforts of neighbours and others to attempt a rescue, which to some extent they were able to do. One reason for this attempted rescue was because of the time lapse in getting fire appliances to the scene. I was informed that there is a Fire Station in Mossley, Ashton u Lyne, but this is only manned during very limited opening hours. I was also informed that there is a significant body of volunteers prepared to act as local volunteer fire officers. Because the fire station was not manned, it took approximately 10 minutes for the fire service to arrive, and whilst this is of course reasonably fast, the local people felt the response time used to be quicker when the local “station” was open. If there is a delay in the arrival of the emergency services, there is always the danger that unqualified people will try to perform a rescue thus placing themselves in danger of injury or even death. ”
    Open source report
  3. Manchester City

    AI-generated summary

    ELIZABETH AURORA KERR · Prevention of Future Deaths report

    This summary was generated using AI from the published report. Please read the original report for the complete account.

    Report summary

    Elizabeth Aurora Kerr died after carbon monoxide from a malfunctioning basement boiler entered the residential flat where she lived, and she was found unconscious several hours after the Fire Service had attended the building. The report identified concerns about the movement and detection of carbon monoxide in buildings, the absence and use of carbon monoxide alarms and gas safety controls, and Fire and Rescue Service equipment, guidance and responses.

    Read the report on judiciary.uk

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Unavailability of carbon monoxide detection equipment on Fire and Rescue Service frontline appliances

    Wider context from the report

    “7. The use and availability of CGI meters by Fire and Rescue Services and having suitable training in their operation as well as the use of personal protective equipment CO alarms. GMFRS did some research in the use of such equipment by all Fire and Rescue Services. Please see the attached. It is suggested that if all Fire and Rescue Services carried such equipment on front line appliances and used them on both emergency responses and preventative work that would reduce the risk of death to Fire Fighters and the public. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Absence of a statutory Fire and Rescue Service role in carbon monoxide safety, regulation and enforcement

    Wider context from the report

    “3. The Role of Fire and Rescue Services in Carbon Monoxide Safety: The Fire and Rescue Services currently have no statutory role in Carbon Monoxide safety, regulation and enforcement. This could be reviewed and considered by the Department for Communities and Local Government. It is appreciated that this is far from straight forward and wider issues would need to be taken into account. For example Fire and Rescue Services have no statutory role in other gases or substances which can cause death. This may require a more detailed analysis and assessment of issues and complications which may then come to light. In the absence of a statutory role, and possibly through the Chief Fire Officers Association “Blue Watch” initiative, Fire and Rescue Services could be encouraged to voluntarily engage in local and national Carbon Monoxide campaigns. Such campaigns may benefit from closer working at a local level with relevant CO charities and at a national level between the Gas Safety Trust, the Gas Safe Charity and the Chief Fire Officers Association. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of suitable training in the operation of carbon monoxide detection equipment

    Wider context from the report

    “7. The use and availability of CGI meters by Fire and Rescue Services and having suitable training in their operation as well as the use of personal protective equipment CO alarms. GMFRS did some research in the use of such equipment by all Fire and Rescue Services. Please see the attached. It is suggested that if all Fire and Rescue Services carried such equipment on front line appliances and used them on both emergency responses and preventative work that would reduce the risk of death to Fire Fighters and the public. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of clear oversight of gas-supplier steps to raise awareness of danger

    Wider context from the report

    “4. Piped Gas Suppliers: It is understood that there are specific conditions of a licence to supply gas as summarised below. It is not clear how gas suppliers define and determine who is a ”vulnerable and priority” customer and how it is established that they have been offered a free annual gas safety check, and have taken advantage (or not) of such an offer ? Nor who actually checks what steps a gas supplier takes in practice to raise the awareness of danger and who judges the reasonability of the steps? ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of clear gas-supplier criteria for identifying vulnerable and priority customers

    Wider context from the report

    “4. Piped Gas Suppliers: It is understood that there are specific conditions of a licence to supply gas as summarised below. It is not clear how gas suppliers define and determine who is a ”vulnerable and priority” customer and how it is established that they have been offered a free annual gas safety check, and have taken advantage (or not) of such an offer ? Nor who actually checks what steps a gas supplier takes in practice to raise the awareness of danger and who judges the reasonability of the steps? ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Failure to identify incomplete flue piping during routine inspections

    Wider context from the report

    “8. The Chief Fire Officers Association “Blue Watch Initiative” This is a voluntary initiative to be encouraged and supported. It offers an independent safety validation service for landlords and letting agents. http://www.bluewatch.co.uk/. The investigation established that incomplete flue piping had not been identified on routine inspection visits despite the regulatory regime created by The Gas Safety (Installation and Use ) Regulations 1988. At present there is no duty imposed on the owner of a boiler or a gas supplier ( who makes a profit from the supply ) that in the case of a multi occupancy building to allow the other occupants , through recognised engineers , to inspect the boiler and be warned to install CO alarms. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of understanding and detailed guidance on the movement of carbon monoxide within buildings

    Wider context from the report

    “2. Guidance on the potential movement of CO within a building: There appears to be a lack of understanding and detailed guidance on the potential movement of CO within a building from its original source and how it can penetrate and move within it. The HSE could provide more information on its web site and provide specific guidance or warnings. There is no HSE guidance to landlords and letting agents as to what independent validation has taken place of the gas and other fuel safety equipment provided in rented property may be appropriate. Such information could also be disseminated to and within all Fire and Rescue Services. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of established monitoring of offers and uptake of free annual gas safety checks

    Wider context from the report

    “4. Piped Gas Suppliers: It is understood that there are specific conditions of a licence to supply gas as summarised below. It is not clear how gas suppliers define and determine who is a ”vulnerable and priority” customer and how it is established that they have been offered a free annual gas safety check, and have taken advantage (or not) of such an offer ? Nor who actually checks what steps a gas supplier takes in practice to raise the awareness of danger and who judges the reasonability of the steps? ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of a duty to warn other occupants to install carbon monoxide alarms

    Wider context from the report

    “8. The Chief Fire Officers Association “Blue Watch Initiative” This is a voluntary initiative to be encouraged and supported. It offers an independent safety validation service for landlords and letting agents. http://www.bluewatch.co.uk/. The investigation established that incomplete flue piping had not been identified on routine inspection visits despite the regulatory regime created by The Gas Safety (Installation and Use ) Regulations 1988. At present there is no duty imposed on the owner of a boiler or a gas supplier ( who makes a profit from the supply ) that in the case of a multi occupancy building to allow the other occupants , through recognised engineers , to inspect the boiler and be warned to install CO alarms. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of regulatory coverage for ongoing maintenance and inspection of existing solid fuel appliances

    Wider context from the report

    “6. The installation , use , maintenance and correct positioning of fixed hard wired or battery operated CO alarms. From October 1st 2010 Building Regulations Approved Document J “Combustion appliances and fuel storage systems” sets out a number of legal requirements in England and Wales. For the first time carbon monoxide (CO) alarms were made mandatory “where a new or replacement fixed solid fuel appliance is installed in a dwelling, a CO alarm should be provided in the room where the appliance is located.” However Building Regulations only concern the processes used during the ‘building’ or ‘installation’ phases, of a solid fuel appliance and do not have any power to talk about on-going maintenance processes or the inspection of existing appliances. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of a duty to allow recognised engineers to inspect boilers in multi-occupancy buildings

    Wider context from the report

    “8. The Chief Fire Officers Association “Blue Watch Initiative” This is a voluntary initiative to be encouraged and supported. It offers an independent safety validation service for landlords and letting agents. http://www.bluewatch.co.uk/. The investigation established that incomplete flue piping had not been identified on routine inspection visits despite the regulatory regime created by The Gas Safety (Installation and Use ) Regulations 1988. At present there is no duty imposed on the owner of a boiler or a gas supplier ( who makes a profit from the supply ) that in the case of a multi occupancy building to allow the other occupants , through recognised engineers , to inspect the boiler and be warned to install CO alarms. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of required audit trails of fuel-supplier carbon monoxide safety steps

    Wider context from the report

    “5. Enforcement and Information: There is no requirement that in the case of a carbon monoxide death, a clear audit trail is available of the steps taken by the relevant fuel supplier to ensure the specific customer in question was aware of the dangers of carbon monoxide poisoning and the benefits of fitting an audible alarm. At the moment there is no specific information that fuel suppliers are required to give. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of HSE guidance to landlords and letting agents on independent validation of gas and other fuel safety equipment in rented property

    Wider context from the report

    “2. Guidance on the potential movement of CO within a building: There appears to be a lack of understanding and detailed guidance on the potential movement of CO within a building from its original source and how it can penetrate and move within it. The HSE could provide more information on its web site and provide specific guidance or warnings. There is no HSE guidance to landlords and letting agents as to what independent validation has taken place of the gas and other fuel safety equipment provided in rented property may be appropriate. Such information could also be disseminated to and within all Fire and Rescue Services. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Greater Manchester Fire and Rescue Service; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of required specific carbon monoxide safety information from fuel suppliers

    Wider context from the report

    “5. Enforcement and Information: There is no requirement that in the case of a carbon monoxide death, a clear audit trail is available of the steps taken by the relevant fuel supplier to ensure the specific customer in question was aware of the dangers of carbon monoxide poisoning and the benefits of fitting an audible alarm. At the moment there is no specific information that fuel suppliers are required to give. ”
    Open source report
Back to top

Published response patterns

Compared with other recipients in reports included in PFD Monitor

Describes published response evidence, not performance.

Published responses found

33%
33%All other recipients 58%
0%100%

How actions were described at the time

This respondent
60%40%
All other recipients
47%25%27%<1%<1%
  • Completed
  • In progress
  • Planned
  • Unclear
  • Partially completed

Statuses reflect what recipients said at the time. PFD Monitor does not verify whether actions happened.

Types of action described in responses

Percentages use all actions described by each group. An action may have more than one type, so percentages do not total 100%.

Information checked against published PFD reports and official responses · Data reviewed 7 Sep 2026 · About data quality and limitations

Data last updated 7 September 2026