Investigation and inquest
On 22nd June 2020 I commenced an investigation into the death of Kenneth Audsley, aged 56. The investigation concluded at the end of the Inquest on Wednesday 8th September 2021. The conclusion of the Inquest was Accidental Death due to Carbon Monoxide Poisoning in the course of his work.
Circumstances of the death
Kenneth Audsley, aged 56 was an experienced high voltage electrical engineer. On Friday 19th June 2020 he was investigating a fault on a large industrial transformer at his place of work when he was overcome by carbon monoxide which had accumulated inside the transformer.
The transformer should have been filled with 2500 litres of oil but in fact held only approximately 170 litres of oil. The carbon monoxide had collected in the space which should have occupied by the oil. The timescale and circumstances in which the oil was lost and the carbon monoxide gas collected in its place have not been established.
Coroner’s concerns
(1) The risk that a potentially lethal gas could accumulate inside the transformer was not appreciated either amongst the electricians in this workplace or those involved with industrial transformers generally.
(2) There were no warning signs affixed to the transformer alerting users to the risk of using the transformer unless it had first been confirmed it contained adequate oil.
(3) The manufacturer’s manual contained no warnings of the hazard which would be created if the transformer were to be energised without containing adequate oil for cooling and insulating purposes.
(4) The manufacturer did not recommend a periodic maintenance regime to confirm adequate oil remained in the transformer and have it replenished if necessary.
(5) By virtue of these matters there exists the possibility that comparable transformers in service throughout the UK may contain insufficient oil to be operated safely and prevent an accumulation of potentially hazardous gases in the space thereby created.
(6) The risks identified could affect anyone (1) dismantling a transformer at the end of its life; (2) having cause to open a transformer for repair or maintenance purposes or (3) users who may be unaware that inadequate oil could cause a transformer to overheat or catch fire.