Recipient

Royal Institution of Chartered Surveyors

First report 10 Oct 2017•Latest report 10 Oct 2017

Recipient record

Reports, concerns and published responses

Private and voluntary organisations · Professional membership body. This page brings together reports naming this recipient and response statements clearly connected to concerns raised in those reports.

Reports
1

Naming this recipient

Published responses
0%

Found for named reports

Concerns addressed
0

Across all linked responses

Stated actions
0

Described in responses

Reports over time

Reports over time

Reports naming this recipient by issue year.

Evidence profile

Report topics

Share of this recipient’s reports compared with all other recipients.

0%published responses found
0stated actions described

Topic comparisons are not available in the current evidence snapshot.

Concerns and recipient responses

Statements from Royal Institution of Chartered Surveyors linked to the concerns in each report. Select any concern, action or position to view the source wording.

  1. Black Country

    AI-generated summary

    Ms Tahnie Lee Martin · Prevention of Future Deaths report

    This summary was generated using AI from the published report. Please read the original report for the complete account.

    Report summary

    Tahnie Lee Martin, aged 29, died after being struck by a large wooden panel that became detached from the roof of the disused Blackrock building during strong winds on 23 February 2017. The principal concerns were that inspections did not identify two hazardous roof structures, and that surveyors were not required to report inaccessible areas or advise clients about the risks of not obtaining access and subsequent inspection.

    Read the report on judiciary.uk

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Royal Institution of Chartered Surveyors; that does not assign responsibility.

    PFD Monitor interpretation

    Failure of building survey reports to identify areas not accessed

    Wider context from the report

    “(1) Although there had been several recent inspections/surveys carried out in respect of the Blackrock building from 2011-2015, none of these had identified the presence of the two structures on the plant room roof. As a result, although steps had been taken to repair/replace other rotten timber and corroded metal structures/fittings on the roof by 23 February 2017, nothing had been done either to remove or to safely maintain the two structures on the plant room roof for at least 19 years, making them inherently unsafe and hazardous. (2) Furthermore, although it seems that the plant room roof would have been difficult to access during these inspections/surveys, none of the Building Surveyors who carried out these or these surveys/inspections had referenced this fact in their reports nor indicated the necessity or urgency of doing so (considering the condition of the main roof generally). I was informed by one of the Building Surveyor witnesses at the inquest that it was not unusual for parts of a commercial building to remain unaccessed during a commercial building survey. Although he, personally, did not consider it acceptable for a Building Surveyor not to mention any areas of a building not accessed (and, indeed, to provide advice about the steps required and cost to achieve this) in the survey report, it appears that: Neither (1) is it a mandatory requirement in the current RICS Guidance Note Building Surveys and Technical Due Diligence of Commercial Property (4th Edition) for a Surveyor to refer to areas of a building not accessed; Nor (2) is it a mandatory requirement for a Surveyor to advise a Client about the specific risks of not obtaining such access and/or subsequent inspection. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Royal Institution of Chartered Surveyors; that does not assign responsibility.

    PFD Monitor interpretation

    Failure to remove or safely maintain structures on the plant room roof

    Wider context from the report

    “(1) Although there had been several recent inspections/surveys carried out in respect of the Blackrock building from 2011-2015, none of these had identified the presence of the two structures on the plant room roof. As a result, although steps had been taken to repair/replace other rotten timber and corroded metal structures/fittings on the roof by 23 February 2017, nothing had been done either to remove or to safely maintain the two structures on the plant room roof for at least 19 years, making them inherently unsafe and hazardous. (2) Furthermore, although it seems that the plant room roof would have been difficult to access during these inspections/surveys, none of the Building Surveyors who carried out these or these surveys/inspections had referenced this fact in their reports nor indicated the necessity or urgency of doing so (considering the condition of the main roof generally). I was informed by one of the Building Surveyor witnesses at the inquest that it was not unusual for parts of a commercial building to remain unaccessed during a commercial building survey. Although he, personally, did not consider it acceptable for a Building Surveyor not to mention any areas of a building not accessed (and, indeed, to provide advice about the steps required and cost to achieve this) in the survey report, it appears that: Neither (1) is it a mandatory requirement in the current RICS Guidance Note Building Surveys and Technical Due Diligence of Commercial Property (4th Edition) for a Surveyor to refer to areas of a building not accessed; Nor (2) is it a mandatory requirement for a Surveyor to advise a Client about the specific risks of not obtaining such access and/or subsequent inspection. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Royal Institution of Chartered Surveyors; that does not assign responsibility.

    PFD Monitor interpretation

    Failure of building inspections and surveys to identify structures on the plant room roof

    Wider context from the report

    “(1) Although there had been several recent inspections/surveys carried out in respect of the Blackrock building from 2011-2015, none of these had identified the presence of the two structures on the plant room roof. As a result, although steps had been taken to repair/replace other rotten timber and corroded metal structures/fittings on the roof by 23 February 2017, nothing had been done either to remove or to safely maintain the two structures on the plant room roof for at least 19 years, making them inherently unsafe and hazardous. (2) Furthermore, although it seems that the plant room roof would have been difficult to access during these inspections/surveys, none of the Building Surveyors who carried out these or these surveys/inspections had referenced this fact in their reports nor indicated the necessity or urgency of doing so (considering the condition of the main roof generally). I was informed by one of the Building Surveyor witnesses at the inquest that it was not unusual for parts of a commercial building to remain unaccessed during a commercial building survey. Although he, personally, did not consider it acceptable for a Building Surveyor not to mention any areas of a building not accessed (and, indeed, to provide advice about the steps required and cost to achieve this) in the survey report, it appears that: Neither (1) is it a mandatory requirement in the current RICS Guidance Note Building Surveys and Technical Due Diligence of Commercial Property (4th Edition) for a Surveyor to refer to areas of a building not accessed; Nor (2) is it a mandatory requirement for a Surveyor to advise a Client about the specific risks of not obtaining such access and/or subsequent inspection. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Royal Institution of Chartered Surveyors; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of mandatory requirements for surveyors to advise clients about risks of unaccessed areas

    Wider context from the report

    “(1) Although there had been several recent inspections/surveys carried out in respect of the Blackrock building from 2011-2015, none of these had identified the presence of the two structures on the plant room roof. As a result, although steps had been taken to repair/replace other rotten timber and corroded metal structures/fittings on the roof by 23 February 2017, nothing had been done either to remove or to safely maintain the two structures on the plant room roof for at least 19 years, making them inherently unsafe and hazardous. (2) Furthermore, although it seems that the plant room roof would have been difficult to access during these inspections/surveys, none of the Building Surveyors who carried out these or these surveys/inspections had referenced this fact in their reports nor indicated the necessity or urgency of doing so (considering the condition of the main roof generally). I was informed by one of the Building Surveyor witnesses at the inquest that it was not unusual for parts of a commercial building to remain unaccessed during a commercial building survey. Although he, personally, did not consider it acceptable for a Building Surveyor not to mention any areas of a building not accessed (and, indeed, to provide advice about the steps required and cost to achieve this) in the survey report, it appears that: Neither (1) is it a mandatory requirement in the current RICS Guidance Note Building Surveys and Technical Due Diligence of Commercial Property (4th Edition) for a Surveyor to refer to areas of a building not accessed; Nor (2) is it a mandatory requirement for a Surveyor to advise a Client about the specific risks of not obtaining such access and/or subsequent inspection. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Royal Institution of Chartered Surveyors; that does not assign responsibility.

    PFD Monitor interpretation

    Failure to indicate the necessity or urgency of accessing unaccessed building areas

    Wider context from the report

    “(1) Although there had been several recent inspections/surveys carried out in respect of the Blackrock building from 2011-2015, none of these had identified the presence of the two structures on the plant room roof. As a result, although steps had been taken to repair/replace other rotten timber and corroded metal structures/fittings on the roof by 23 February 2017, nothing had been done either to remove or to safely maintain the two structures on the plant room roof for at least 19 years, making them inherently unsafe and hazardous. (2) Furthermore, although it seems that the plant room roof would have been difficult to access during these inspections/surveys, none of the Building Surveyors who carried out these or these surveys/inspections had referenced this fact in their reports nor indicated the necessity or urgency of doing so (considering the condition of the main roof generally). I was informed by one of the Building Surveyor witnesses at the inquest that it was not unusual for parts of a commercial building to remain unaccessed during a commercial building survey. Although he, personally, did not consider it acceptable for a Building Surveyor not to mention any areas of a building not accessed (and, indeed, to provide advice about the steps required and cost to achieve this) in the survey report, it appears that: Neither (1) is it a mandatory requirement in the current RICS Guidance Note Building Surveys and Technical Due Diligence of Commercial Property (4th Edition) for a Surveyor to refer to areas of a building not accessed; Nor (2) is it a mandatory requirement for a Surveyor to advise a Client about the specific risks of not obtaining such access and/or subsequent inspection. ”
    Open source report

    Source evidence

    How this individual concern was interpreted

    PFD Monitor created a concise, searchable interpretation from the report wording shown below. The report was sent to Royal Institution of Chartered Surveyors; that does not assign responsibility.

    PFD Monitor interpretation

    Lack of mandatory requirements for surveyors to refer to areas of a building not accessed

    Wider context from the report

    “(1) Although there had been several recent inspections/surveys carried out in respect of the Blackrock building from 2011-2015, none of these had identified the presence of the two structures on the plant room roof. As a result, although steps had been taken to repair/replace other rotten timber and corroded metal structures/fittings on the roof by 23 February 2017, nothing had been done either to remove or to safely maintain the two structures on the plant room roof for at least 19 years, making them inherently unsafe and hazardous. (2) Furthermore, although it seems that the plant room roof would have been difficult to access during these inspections/surveys, none of the Building Surveyors who carried out these or these surveys/inspections had referenced this fact in their reports nor indicated the necessity or urgency of doing so (considering the condition of the main roof generally). I was informed by one of the Building Surveyor witnesses at the inquest that it was not unusual for parts of a commercial building to remain unaccessed during a commercial building survey. Although he, personally, did not consider it acceptable for a Building Surveyor not to mention any areas of a building not accessed (and, indeed, to provide advice about the steps required and cost to achieve this) in the survey report, it appears that: Neither (1) is it a mandatory requirement in the current RICS Guidance Note Building Surveys and Technical Due Diligence of Commercial Property (4th Edition) for a Surveyor to refer to areas of a building not accessed; Nor (2) is it a mandatory requirement for a Surveyor to advise a Client about the specific risks of not obtaining such access and/or subsequent inspection. ”
    Open source report
Back to top

Published response patterns

Compared with other recipients in reports included in PFD Monitor

Describes published response evidence, not performance.

Published responses found

0%
0%All other recipients 58%
0%100%

How actions were described at the time

This respondent
All other recipients
47%25%27%<1%<1%
  • Completed
  • In progress
  • Planned
  • Unclear
  • Partially completed

Statuses reflect what recipients said at the time. PFD Monitor does not verify whether actions happened.

Types of action described in responses

Percentages use all actions described by each group. An action may have more than one type, so percentages do not total 100%.

Information checked against published PFD reports and official responses · Data reviewed 7 Sep 2026 · About data quality and limitations

Data last updated 7 September 2026