PFD report

Mr. George Hines · Prevention of Future Deaths report

Pin Get email alerts Request correction

Issued 27 Oct 2015•Avon

Report record

Published report and response evidence

This page connects the concerns raised in this report with statements found in recipients’ published responses. A link shows a clear evidence connection; it does not assign responsibility.

View original report
Concerns
5

Raised in this report

Recipients
1

Named on the report

Responses found
0

Of 1 recipient

Stated actions
0

Described in responses

Recipients and published responses

Source document

Full report text

This is the full text from the original published report.

Open published report

Concerns and recipient responses

Select any concern, action or position to view the source wording.

Report evidence summary

Concerns raised5

  1. Failure to provide regular inspection, testing and maintenance of smoke detectors
  2. Failure of smoke detectors to alert the Emergency Control Room and communal areas
  3. Unavailability of a communal-area pull-cord
Responses linked to these concerns

Each statement is shown once, even when linked to more than one concern.

No linked response statements

No respondent-stated action or position is clearly linked to these concerns.

Source evidence

How this individual concern was interpreted

PFD Monitor created a concise, searchable interpretation from the report wording shown below. Response links show a clear evidence connection; they do not assign responsibility.

PFD Monitor interpretation

Failure to provide regular inspection, testing and maintenance of smoke detectors

Wider context from the report

“(2) There was a recently installed smoke detector system with battery back up. The Fire Investigation Officer confirmed the smoke detector was probably functioning correctly at the time of the fire. The previous stand alone battery smoke detector was also in place. The evidence given to the Inquest was that it was the responsibility of the resident to regularly test the smoke detector and replace the battery as necessary, notwithstanding the flat was sheltered accommodation and the deceased was elderly. The Council should implement a regular programme of its own inspection, testing and maintenance of the smoke detector. ”

Is this part of a recurring concern?

No recurring-concern membership is currently published.

Open source report

Source evidence

How this individual concern was interpreted

PFD Monitor created a concise, searchable interpretation from the report wording shown below. Response links show a clear evidence connection; they do not assign responsibility.

PFD Monitor interpretation

Failure of smoke detectors to alert the Emergency Control Room and communal areas

Wider context from the report

“(3) The flat has a pull-cord alarm system which is connected 24 hours a day to an Emergency Control Room. The recently installed smoke detector alarms only in the individual resident’s flat and not elsewhere in the building and does not automatically in the ECR. The smoke detector did not alert other residents to the fire. The Council should consider connecting the smoke detector to the alarm system installed in each flat as well as ensuring it also alarms in the communal area. ”

Is this part of a recurring concern?

No recurring-concern membership is currently published.

Open source report

Source evidence

How this individual concern was interpreted

PFD Monitor created a concise, searchable interpretation from the report wording shown below. Response links show a clear evidence connection; they do not assign responsibility.

PFD Monitor interpretation

Unavailability of a communal-area pull-cord

Wider context from the report

“The current advice to residents on discovering a fire is to leave their flat and alert the emergency services by pulling the emergency cord in the communal area or in a neighbour's flat. The Inquest heard evidence there was no pull-cord in the communal area of this building. The residents are also instructed that the alternative to pulling the five cord was that they should dial 999. Instructions to residents to pull the cord first may give a false sense of security that the emergency services have been alerted even if they receive no audible response from the ECR. The Council should revise its instructions to residents in the event of fire generally and specifically that they are instructed to dial 999 first before taking any other action. ”

Is this part of a recurring concern?

No recurring-concern membership is currently published.

Open source report

Source evidence

How this individual concern was interpreted

PFD Monitor created a concise, searchable interpretation from the report wording shown below. Response links show a clear evidence connection; they do not assign responsibility.

PFD Monitor interpretation

Failure of fire instructions to require residents to dial 999 first

Wider context from the report

“The current advice to residents on discovering a fire is to leave their flat and alert the emergency services by pulling the emergency cord in the communal area or in a neighbour's flat. The Inquest heard evidence there was no pull-cord in the communal area of this building. The residents are also instructed that the alternative to pulling the five cord was that they should dial 999. Instructions to residents to pull the cord first may give a false sense of security that the emergency services have been alerted even if they receive no audible response from the ECR. The Council should revise its instructions to residents in the event of fire generally and specifically that they are instructed to dial 999 first before taking any other action. ”

Is this part of a recurring concern?

Yes — Unreliable fire-response instructions for residents.

Open source report

Source evidence

How this individual concern was interpreted

PFD Monitor created a concise, searchable interpretation from the report wording shown below. Response links show a clear evidence connection; they do not assign responsibility.

PFD Monitor interpretation

Failure to inspect and maintain pull-cords in working order

Wider context from the report

“(1) The pull-cord in the bedroom of the deceased was found by the Fire Investigation Officer not to be connected to the ceiling switch. Notwithstanding the regular visits by the HSA this fact was not noted and no corrective action had been taken. No evidence of a regular planned preventative maintenance programme was given to the Inquest with regard to ensuring all pull-cords were working and in good order. The Council should implement a regular inspection and maintenance programme for the alarm system if not already in place. ”

Is this part of a recurring concern?

No recurring-concern membership is currently published.

Open source report